1.Product usage
The M8LC series residual current operated circuit breaker(hereinafter referred to as circuit breaker) is mainly suitable for distribution networks with frequency of AC 50Hz and rated working voltage of AC 400V.Used in three-phase four-wire power supply and consumption system with neutral point directly grounded, it has functions such as overload, short circuit, phase loss, overvoltage, undervoltage, residual current action protection, etc. It can protect circuit and electrical equipment from damage, and also provide protection for possible grounding fault and indirect personal contact in circuit.
The product complies with GB/T14048.2,GB/T14048.4,GB/T32902 and GB/T22387 standard.
2.Product feature
2.1 Multiple functions
It has protection functions such as residual current, overcurrent, short circuit, etc, as well as practical functions such as automatic reclosing, residual current display, realtime load current display, action status indication and trip data display. The product also has functions such as pluggable lightning protection module, four remote functions and special adapter.
2.2 Small volume
The combination of electric operating mechanism and air circuit breaker has been transformed into an integrated type, with reduced installation location and simplified wiring. The operation method with configurable function characteristic can set the
required functions such as action current, breaking time and main circuit current according to the actual situation.
2.3 Intelligence
The intelligent control circuit composed of single chip microprocessor can set and display load current, monitor the cause of fault trip, display fault parameters during trip, and query the total number of various fault trips.
2.4 Communicability (when this function is required during ordering)
The communication type leakage circuit breaker can record and query detailed data such as the phase sequence that causes the trip, cause and trip time, and has the function of historical data recording; the communication series product adopts RS-485 communication port and have multiple communication protocols to choose from. It can establish communication function with intelligent distribution transformer terminal, upper computer, etc., and achieve remote parameter adjustment, information query and fault parameter download.
3.Working environment and installation condition
The ambient air temperature shall not exceed +40℃, and the average temperature value within 24 hours shall not exceed +35℃. The lower limit of the ambient air temperature is -20℃; Note: For working condition where the ambient air temperature is above +35℃ or below -20℃, the user should consult with the manufacturer.
The altitude of the installation site shall not exceed 2000m;The maximum temperature is +40℃, and the relative humidity of the air does not exceed 50%. At lower temperature, there can be higher relative humidity. Special measures should be taken for occasional condensation caused by temperature changes;In a place without rain or snow erosion;
The pollution level is 3;
The maximum inclination of circuit breaker installation is ±5°;Installation category: The installation category of the main circuit of the circuit breakeris III, and the installation category of the auxiliary circuit and control circuit is II.
The external magnetic field of the installation site shall not exceed 5 times the geomagnetic field in any direction.
4.Model and meaning
5. Main technical parameter
|
Model and specification |
M8LC-125 |
M8LC-250 |
M8LC-400 |
M8LC-630 |
M8LC-800 |
|
Frame current In(A) |
125 |
250 |
400 |
630 |
800 |
|
Overload long delay |
(0.4~1)In |
||||
|
Rated residual operating |
30 (non delay type only) |
||||
|
Ultimate non driving time (s) |
0.06 0.1 0.2 optional settings |
||||
|
Number of poles |
3P+N; 4P |
||||
|
Rated insulation voltage Ui(V) |
AC1000 |
||||
|
Rated impulse withstand |
125/250/ 8KV 400/630/800 12KV |
||||
|
Rated working voltage Ue(V) |
AC380/400/415 50Hz |
||||
|
Rated ultimate short-circuit |
M50/H85 |
M65/H85 |
M65/H85 |
||
|
Rated service short-circuit |
M35/H65 |
M50/H65 |
M50/H65 |
||
|
Rated short time withsatnd current Icw |
5kA/1S |
10kA/1S |
10kA/1S |
||
|
Selective category |
Category B |
Category B |
Category B |
||
|
Rated residual short-circuit making |
25%Icu |
||||
|
Reclosing interval time (s) |
20~60(manual closing is not limited by time interval) |
||||
6. Outline and installation dimensio
|
Specification |
Outline dimension mm |
Installation dimension mm |
External copper plate dimension |
Installation screw dimension mm |
||||
|
W |
L |
H |
A |
B |
D |
C |
||
|
M8LC- 125 |
122 |
220 |
122 |
199 |
60 |
30 |
16 |
4x45 |
|
M8LC -250 |
142 |
240 |
135 |
201 |
70 |
35 |
22 |
|
|
M8LC-400(630ZR) |
196 |
335 |
177 |
272 |
96 |
48 |
30 |
6X70 |
|
M8LC-800 |
240 |
355 |
187 |
285 |
116 |
58 |
40 |
|
Note: The mounting hole cut-out size is the reference size, and the customer can adjust the actual cut-out size according to the installation method.
6.1 The circuit breaker should be installed vertically and fixed with screw through the mounting hole.
6.2 The user selects standard cross-sectional area wire based on product current specification and connect the wire to the circuit breaker(the copper connector must be equipped). The upper terminal of the circuit breaker(right zero 1,3,5,N;left zero N, 1, 3, 5)is the power input terminal of the main circuit, and the lower terminal(right zero 2,4,6,N; left zero N,2,4,6)is the output terminal. The neutral line(zero line) of the power supply must be connected to the "N" terminal.
6.3 After installation, power on the circuit breaker. If the status indicator light is not on, it indicates that it is in the disconnected state. Press the "Closing" button to start the circuit breaker closing. When the "Closing" status indicator light is on, it indicates successful closing.
7.Description of protection characteristic
7.1 Digital tube type
7.1.1 Action value setting range
Table 1: Overload long delay parameter setting
7.1.2 Action characteristic
Table 2: Protection action characteristic
7.1.3 Delay characteristic
Overload protection is carried out according to the inverse time limit characteristic:T=(6Ir1/I)2tL Delay precision:±10% Among which, T is the action time value, Ir1 is the set value for long delay protection, I is the fault current, and tL is the set value for long delay time
7.2 Short circuit short delay protection
Short circuit short delay protection prevents impedance short circuit in the distribution system, and trip delay is to achieve selective protection.
7.2.1 Short circuit short delay protection related parameter setting
Table 3: Short circuit short delay parameter setting
| Parameter setting | Set value | Factory set value | ||||||
| Short delay action current set value Ir2 |
2Ir2~10Ir2 adjustable | 6Ir2 | ||||||
| Short delay time set value ts |
0.1s-1.0s adjustable | 0.4s | ||||||
7.2.2 Short circuit short delay protection action characteristic
Table 4: Short circuit short delay action characteristic
| Characteristic | Fault current multiple | Trip time | Delay error |
| Non-action characteristic |
≤0.85Ir2 | Non-action | +40ms |
| Action characteristics |
>1.15Ir2 | Delay action | +40ms |
7.3 Instantaneous protection
7.3.1 Short-circuit instantaneous protection related parameter setting
Table 5: Instantaneous parameter setting
| Parameter setting | Factory set value | |
| Instantaneous action current set value Ir3 |
4li-12li adjustable | 10Ir1 |
7.3.2 Short circuit instantaneous protection action characteristic
Table 6: Instantaneous action characteristic
| Characteristic | Current multiple (I/Ir3) | Trip time | Delay error |
| Non-action characteristic |
≤0.8 | Non-action | - |
| Action characteristics |
>1.2 | Instantaneous action | - |
7.4 Residual current protection characteristic
7.4.1 Gear setting range
| Parameter | Set value(mA) | Factory set value |
| Residual operating current I n |
30 (non-delay only) 50/100/150/200/300/500/700/900/1000/OFF graded adjustment(delay type), automatic tracking |
500mA |
7.4.2 Action characteristic
7.4.3 Automatic gear mode
Gear value and floating value in automatic gear mode:
When the residual current exceeds the floating value of the gear but does not reach its operating value and remains stable for 60s, the gear will float up one gear, and so on, until the maximum gear is reached; when the residual current is less than the floating value of the next gear and remains stable for 120s, the gear will float down one gear, and so on until the minimum gear is reached. Taking the "Automatic 2" gear as an example, the initial residual current of the line is 100mA. When the circuit breaker is energized and the gear is automatically set to 300mA. When the residual current increases to above 150mA and stabilizes for 60s, the gear changes to 500mA gear; when the residual current decreases to below 150mA and stabilizes for 120s, the gear changes to 200mA.
8. Characteristic curve of electronic type overcurrent short circuit protection
9.Panel introduction
9.1 Meaning of status indicator light
(1)Power light: it indicates the power supply status
(2) "Closing" light: After the circuit breaker is closed, the "Closing" light will light up.
(3)"Fault light": When there is undervoltage, phase failure, overvoltage, current fault and manual opening, the light will light up.
(4)Communication light: When there is communication function, the communication light flashes.
(5)Alarm light: When the leakage alarm function is activated, the alarm light is on, and the light flashes when the leakage exceeds the set value.
9.2.2Key description
(1) [Opening]key: Press this key to enter the opening state of the controller.
(2) [Closing]key: Press this key to automatically turn on the controller.
(3) [Return]key: Press this key to exit the parameter setting state and enter the normal detection operation state.
(4) [Settings]Key: Press this key to enter the parameter setting state and perform parameter setting.
(5) [Up, Down]keys: The user can select the desired option in the menu.
(6) [Confirm]key: After setting the parameter, press this key to save the setting.
(7) [Test trip]key: Press this key to simulate a leakage fault and the controller will turn off.
10. Introduction to the operation interface
10.1 Digital tube type
10.1.1 Main menu
Press the Menu key to enter the menu interface, as follows:
1. Function setting ( ) 2. Parameter settings ( ) 3. Fault recording( )
4. Number of faults ( ) 5. Self check setting( ) 6.Factory maintenance( )
10.1.2 Under function setting ( ), press Confirm and enter the
password(initial: 0000) to enter the function setting interface. Press the
or keys to select the function setting item, press the Menu key, the
value will remain on, and then press Confirm to activate the function. The
flashing display of the parameter indicates that the function is in the exit state,
and the constant illumination of the parameter indicates that the function is in
use. As shown in Figure 7, the leakage alarm is turned on. Press the Return
key to return to the menu interface.
| Function setting | Default value | |
| Leakage alarm | OFF | After the leakage alarm function is turned on: flashing: it indicates that the leakage is greater than the set value, constantly on: it indicates that the leakage alarm function has been turned on. (Note: Long press and hold the Return button for 3s to turn on or off the leakage alarm function. When the leakage alarm function is turned on, the product only alarms and does not trip.) Warning: The leakage alarm function cannot be activated without the approval of the power supply management department |
| Automatic tracking | OFF | |
| Abrupt change protection | OFF | |
| Special wave protection | OFF | |
| Automatic closing | ON | |
| Power-on test closing | ON | |
| Overvoltage protection | ON | |
| Undervoltage protection | OFF | |
| Phase failure protection | OFF | |
| Full voltage loss function | ON | |
| Current protection function | ON | |
| Short circuit short delay function setting | ON | |
| Current imbalance | OFF | |
| Zero line loss protection function | OFF | |
| External breaking function | ON | For maintenance personnel only |
10.1.3 Under parameter setting ( ), press Confirm and enter the
password(initial:0000) to enter the parameter setting interface. Press Confirm ,
the value will flash, press the or keys to modify the parameter, and
press the Confirm key to confirm the parameter. As shown in Figures 8 and 9,
press the Return button to return to the menu interface.
10.1.4 Under fault record( ), press Confirm to enter the fault and trip
information query interface. Press the Confirm key to enter the fault cause, and
press the Menu to inquire about the trip cause and time. As shown in Figures 10
and 11, press the Return button to return to the main menu interface.
10.1.5 Under number of faults ( ), press Confirm to enter the fault
frequency query interface. It will display the total number of trips and the number
of blocked trips. As shown in Figures 12 and 13. Press the Return key to return
to the main menu interface.
10.1.6 Factory maintenance( ) is only for the manufacturer's technical and
maintenance personnel to operate.
10.2 Liquid crystal type
10.2.1 It displays product version information upon startup
This interface mainly displays software and hardware version information
10.2.2 Real time information display
This interface mainly displays the operating status of the switch, real-time voltage, real-time current, real-time leakage, leakage gear and system time ->00/02: it indicates the number of leakage/blocking times
Button operation instruction
Up/Down :Page flipping display
Menu : it enters the main menu
10.2.3 Main menu
This interface is the main menu, and various submenus can be accessed
from this interface
Button operation instruction
Up/Down : It moves the cursor
Menu : It enters submenu
Return : It returns to the real-time display interface
10.2.4 Login interface
The default password is 0000 (press the Confirm button 4 times continuously)
Button operation instruction
Up/Down :It moves the selection cursor
Confirm : It enters password
Return : It returns to the main menu
10.2.5 Parameter setting interface
Under this interface, the user can set the opening and closing of various functions
Button operation instruction
Set : It moves the setting item cursor
Confirm : It enters/exits(parameter storage)setting status
Up/Down : Setting adjustment
Return : It returns to the main menu
10.2.6 Parameter setting interface
Set the functional parameters on this interface, and then press the Confirm
button to save the operation instruction
Up/Down :It moves the setting item cursor
Confirm : It enters/exits(parameter storage)setting status
Return : It returns to the main menu
10.2.7 Fault record interface
This interface can query the historical event record of the switch, as well as the fault voltage, current and leakage data at the time of the event occurrence, as well as the specific time of the event occurrence.
Button operation instruction
Up/Down : It switches record information
Return : It returns to the main menu
10.2.8 Number of faults interface
This interface displays the total number of trips, blocking trips, leakage trips, and overcurrent trips.
Button operation instruction
Return : It returns to the main menu
10.2.9 Factory maintenance menu
Under this menu, the parameter coefficient can be fine tuned
Note: This function is used for internal debugging within the company and is not recommended for non special circumstances
11.Common fault display
11.10 Opening failure, as shown in Figure 24 on the screen;
12. Precaution
12.1 After the residual current circuit breaker is put into normal operation, it
should be tested once a month and recorded.
12.2 It is not allowed to test trip by short circuiting the phase line to the
neutral line to avoid causing short-circuit current and burning the device. A
resistor of about 1KΩ should be connected in series (determined according to
regulation).
12.3 Protection cannot be provided for electric shock hazards caused by
simultaneous contact with two wires of the protected circuit.
12.4 Do not unseal the circuit breaker without authorization, otherwise you
should bear the consequences.
13. Description of external terminals
External port description:
Due to customer customization or standard change, the external port may not be consistent with the figure below. Please
refer to the terminal label on the product body for accuracy. We apologize for any inconvenience caused. The external terminals are shown in the figure
14. Common fault analysis and troubleshooting method
| Fault category |
Fault phenomenon | Cause analysis | Troubleshooting method |
| Unable to put into operation |
Indicator light does not light up |
1. Check if the power supply is connected properly 2. The controller switch is not . turned on |
1. Connect the power supply properly. 2. Turn on the controller switch |
| When pressing the "Close" button, the circuit breaker cannot be closed |
1. Check whether the zero line is connected to “N” terminal 2. The controller switch is not turned on |
1. Check the zero line 2. Turn on the controller switch |
|
| It trips immediately after closing |
1.Mixed use of zero and ground line 2. Excessive load leakage 3. Undervoltage, overvoltage and phase loss |
1. Check the circuit and electrical equipment. 2. Check the circuit for leakage fault. 3. Check the circuit for fault or turn off relevant protection |
|
| Refusal to move |
When pressing the test button, it doesn't trip |
1. Controller switch is not turned on 2. Leakage function is turned off |
1. Turn on the controller switch 2. Turn on the leakage protection function |
| When pressing the test button, it can trip, but it does not trip the actual bulb test |
The neutral point of the distribution transformer is not grounded or has poor contact |
Check neutral grounding |
Dear users:
The leakage alarm function is enabled and is only used by professional personnel for maintenance. It is prohibited to start after the product is put into normal operation
15. Accessory list
1. 1 operating manual;
2. 1 manual wrench;
3. 6 arc barriers;
4. Mounting screws;
5. 1 7P wiring terminal.