DAB6-125 is such features as delicate appearance, light weight, excellent and reliable performance, high breaking capacity, rapid tripping and mounted by rail. Its enclosure and com-ponents adopts high fire-retarding and shock-resistance plastic of long durability. It mainly serves for protecting the circuits of AC 50Hz, 230V of single pole, 400V of two poles or three or four poles from overload or short-circuit, and also for unfrequented making and breaking electrical apparatus and lighting circuit.It conforms with the standards of IEC60947-2.
Product Description
● Two types of overload and short circuit protection.
● Independent contact position indicator.
● DIN rail latch with a double fixed position.
● Wide range of operating temperatures from –40 to +50° С.
● Updated wider engagement lever with improved contact area.
● Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.
● Higher switching capacity of 10 kA provides for installing DAB6-125 as incoming circuit breakers.
Specifications
|
MCB DAB6-125 |
|||||||
|
For protection of general power distribution (IEC/EN 60898-1) |
|||||||
|
Poles |
1P |
2P |
3P |
4P |
|||
|
Electrical performance |
|||||||
|
Functions |
short circuit protection,overload protection,isolationg,control |
||||||
|
Rated frequency f(Hz) |
50-60Hz |
||||||
|
Rated working voltage Ue(V) AC |
230/400 |
400 |
|||||
|
Rated current In(A) |
63,80,100,125 |
||||||
|
Rated insulated voltage Ui (V) |
500 |
||||||
|
Impulse withstand voltage Uimp( kV) |
4 |
||||||
|
Instantaneous tripping type |
DAB6-125N |
B/C/D |
|||||
|
|
DAB6-125H |
B/C/D |
|||||
|
Rated short circuit Icn(kA) |
DAB6-125N |
6 |
|||||
|
|
DAB6-125H |
10 |
|||||
|
Release type |
Thermal magnetic type |
||||||
|
Service life(O~C)
|
Mechanical |
Actual value |
8500 |
||||
|
Standard value |
4000 |
||||||
|
Electrical |
Actual value |
1500 |
|||||
|
Standard value |
1000 |
||||||
|
Connection and installation |
|||||||
|
Protection degree |
IP20 |
||||||
|
Wire(mm²) |
1~35 |
||||||
|
Working temperature |
-5~+40℃ |
||||||
|
Resistance to humidity and heat |
Class 2 |
||||||
|
Altitude above sea |
≤2000 |
||||||
|
Relative humidity |
+20℃ ,≤90% ;+40℃ ,≤50% |
||||||
|
Pollution degree |
2 |
||||||
|
Installation environment |
Avoid obvious shock and vibration |
||||||
|
Installation class |
ClassⅡ , ClassⅢ |
||||||
|
Mounting |
DIN35 rail |
||||||
|
Dimensions(mm) (WxHxL) |
a |
27 |
54 |
81 |
108 |
||
|
b |
80 |
80 |
80 |
80 |
|||
|
c |
73 |
73 |
73 |
73 |
|||
The over-current protection property
|
Ambient Temperature |
Initial Status |
Test Current |
Expected Result |
Expected Result |
NOte |
|
40±2oC |
Cold position |
1.05In(In≤63A) |
t≤1h |
Non-release |
– |
|
Cold position |
1.05In (In[63A) |
t≤2h |
Non-release |
– |
|
|
Carried out immediately after previous test |
1.30In(In≤63A) |
t < 1h |
Release |
Current smoothly rises to specified value within 5s |
|
|
1.30In (In>63A) |
t < 2h |
Release |
|||
|
-5~+40oC |
Cold position |
8.00In |
t≤0.2s |
Non-release |
– |
|
Cold position |
12.00In |
t< 0.2s |
Non-release |
– |
Applicable conducting wire
|
Rated current(A) |
Nominal cross section of wire mm2 |
|
63A |
16 |
|
80A |
25 |
|
100A |
35 |
Product Features