Specifications
· Normal installation conditions
>> The circuit breakers DAA all be installed in accordance with the manufacturer’s instructions.
The vertical inclination of the circuit breakers DA All not exceed 5°
· Installation category
| Rated operational voltage | 380/400V | 660/690V |
| Installation category | ||
| Electric circuit | ||
| Main circuit | IV | IV |
| Coil of under voltage release | ||
| Primary coil power transformer | ||
| Auxiliary circuit | III | III |
| Degree of protection | Installation method | Accessories |
| IP30 | Normal open mounting | |
| IP40 | Mounted in a compartment of cubicle with additional door frame | Door frame to be mounted by user |
| IP54 | Mounted in a compartment of cubicle with additional door frame and transparent cover | Door frame and transparent cove to be mounted by user |
| Type | DAA1-1000 | DAA1-2000 | DAA2-3200 | DAA3-4000 | DAA4-6300 | |
| Frame rated | 1000 | 2000 | 3200 | 4000 | 6300 | |
| current Inm(A) | ||||||
| Number of poles | 3,4 | 3,4 | 3,4 | 3,4 | 3,4 | |
| Rated current In(A) | 200,400,630,800,1000 | 400,630,800,1000,1250,1600,2000 | 2000,2500,3200 | 4000 | 50,006,300 | |
| Icu(kAO-co | 40 OV | 42 | 80 | 100 | 100 | 120 |
| 69 OV | 25 | 50 | 65 | 65 | 85 | |
| Ics(kA)O-Co-co | 40 OV | 30 | 50 | 65 | 65 | 100 |
| 69 OV | 20 | 40 | 50 | 50 | 80 | |
| IcwlkA)o-co | 40 OV | 20 | 50 | 65 | 65/80(MCR) | 85/100(MCR) |
| 69 OV | 20 | 40 | 50 | 50/65(MCR) | 65/75(MCR) | |
| Rated current at N-pole In(A) |
50%ln,100%ln | |||||
| Inherent making& breaking time |
23-32ms | |||||
| Operational peformance (operations) |
Electric life |
500 | ||||
| Mechanical life | 9500 | |||||
| Mounting mode | Fixed with draw-able | |||||
| Arcing distance(mm) | 0 | |||||
| Intelligent controller | Standard type(M) Telecommunication type (H) | |||||
| Long delay | short delay | Instantaneous | Ground Fault | |||||
| Ir1 | Ir2 | error | Ir3 | error | error | Ir4 | error | |
| (0.4-1)In | (0.4-15)In | ±10% | In~50kA(Inm=2000A) In~75kA(Inm=3200~4000A) In~100kA(Inm=6300A) |
±15% | ±15% | Inm=2000~4000A (0.2~0.8)In Max 1200A, Min 160A |
Inm=6300A (0.2-1.0)In |
±10% |
| 1.05Ir1 | 1.3Ir1 | 1.5Ir1 setting time (s) | 15 | 30 | 60 | 120 | 240 | 480 |
| >2h non-operation | <1h opetation | 2.0Ir1 opetation time (s) | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |