Specifications
| Pole Number | 1,2,3,4 |
| Standard | IEC60947-3 |
| Rated Current of Structure Design | 32A |
| Voltage and Frequency | 230/240V~, 50/60Hz |
| Rated Current | 63-125A |
| Insulation voltage Ui | 500V |
| Rated short circuit making capacity | 20le, t=0.1s |
| Electrical life | 1500 |
| Mechanical life | 8500 |
| Pollution degree | 2 |
| Terminal connection type | Cable busbar |
| Tightening torque | 3.5Nm |
| Rated shot-time withstand current Icw | 12le 1s |
| Uilization category | AC-22A |
Overall&Installation Dimensions
Installation and use instructions and notes for attention
● The DIN-rail installation micro change-over switch should be installed
vertically, with the upper terminal connected with the power source and the
dynamic contact de-energized when disconnected soars to ensure the human safety
during manual operation.
● Normally, the DIN-rail installation micro change -over switch should not be operated with load during switching -on and off.
● The upper end is for incoming line and the lower end for outgoing line
(load terminal), reverse connection is not allowed. If it is necessary to cut
off the power of position I and II, when the handle is pushed to the position O,
the position I and II are all in powered off state. If position II is to be
activated, push the handle upward, then the contact of position II is
connected,and that of position I is disconnected; if position I is to be
activated, pull the handle downward, then the contact of position I is
connected, while that of position II is disconnected.
● The 3- position changeover of the product is realized through the
operation of mechanical parts relying on the compression and release of the main spring. The handle needs high operating force and shows big inertia force
(63A-125A product), usually, it is difficult to realize e accurate changeover
with a single hand, and the improper operation will cause abnormal changeover
of the circuit. During use, it is recommended to operate 63A-125A product with
both hands or with accessories provided by the factory (the extend operating
handle).
● The DIN-rail installation micro change-over switch should not be applied
with over-current during connection and disconnection (use under overload),nor
cut on and off with normal working current. Never push or pull the switch with
strong force in order to avoid any accident or reduction of the service
life.
● If several change- over switches are put into the closed distribution
box at same time, heat may be accumulated in the box, as a result, the
temperature will rise and the switch will get extremely hot. After long time of
use, the insulating parts of the products will be damaged and the service life
of the product will be reduced. When the temperature reached over + 40C, the
product should berated. If the derating factor is 0.8. then the maximum
working current shall be the rated current multiplied by the factor 08 (for
example: the maximum working current 125Ax 0.8= 100A).
● The DIN-rail installation micro change – over switch has no arc
extinguishing chamber. It is not allowed to use it for breaking fault current.
If necessary, the customer can select proper fuse combination to make available big load and short circuit breaking capacity (the concrete breaking
capacity is decided by the breaking ability of the fuse selected).The section
area of the connecting wire of change-over switch should match the rated current
so as to ensure the normal use of the product. The torque of product wire:1.2 N. mat 16-40A.
● During the use, the connecting terminals of the switch and wires should
be checked if they are well fastened with screws. If the terminals change
color.
| Rated current (A | 16-20A | 25A | 32A | 40-50A | 63A | 8GA | 100A | 125A |
| Wire speoficaton | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 |
Product Features
The DIN-rail installation micro change-over switch realizes the changeover of O, l and Il positions directly with manual handle. The turning slot of the internal handle and the sliding position of the spindle are all coated with high grade lubricant to reduce mechanical wear. The dynamic and static contact adopt the reasonable contact method with good conductivity and stability. The modular and standard guide installation structure is particularly suitable for the matching circuit of terminal combination apparatus.
Specification and Feature: